Flow meters
Flow meters typically come in two varieties- pulse output
or 4-20 milliamp DC current output. Either the pulse signal or 4-20 mA signal
is connected to the proper input on the Micro-Comm
PLC.
A
pulse output type flow meter means that a single DC pulse
from the meter represents a number of gallons. Based
on the manufacturer, a single pulse could represent one gallon or as many as
ten per pulse. Usually this information is printed on the meter head or
elsewhere in the documentation. Testing of a pulse type meter connected to a
Micro-Comm RTU will require the use of a voltmeter that has the capability to measure frequency
in hertz. The frequency is cycles per second, so to calculate GPM, multiply the
frequency reading on the voltmeter by 60. Then, multiply by the pulse per
gallon number specified by the flow meter manufacturer.
The
4-20 mA type flow
meter will provide a flow rate where 4 milliamps is zero flow and 20
milliamps is the full scale output. Any current in
between algebraically can be calculated to represent gallons per minute. To calculate flow, use a voltmeter set to read DC milliamps. Take the number
you read and subtract 4. Divide that number by 16 and you will have a
decimal/percentage. Multiply that percentage by the full
scale output of the meter to determine the current flow rate.
Example:
Your measurement shows 11.23 milliamps. Full scale output
of the flow meter is 1000 gallons per minute.
11.23 mA subtract 4 = 7.23 mA
7.23 divided by 16 = .452
.452 X 1000 = 452 gallons per minute.
Troubleshooting
It is rare that a flow meter will give erroneous readings,
although it does happen. More often, a pulse
type meter will break and not give any signal at all. A 4-20 mA output meter may give a low
value like zero, or well below the 4mA minimum. In some cases, the meter may
put out current in excess of 20mA. In any case, if you
read current well above 20mA or below 4mA, there is most likely a problem with
the meter output unit.
M1500, M1550, M1650, S3000, S4000, S4500 and similar PLC’s
have a light associated with the pulse input that will flash when the RTU is
receiving a pulsing signal from the flow meter. Consult your RTU drawing to
determine exactly where the flow meter in question is wired in so you can
verify the correct light is flashing.
The only valid way to test a 4-20mA signal is by use of a voltmeter described above.
More information about
flow meter diagnosis is available here
Copyright
2018 Micro-Comm Inc. 15895 S. Pflumm Road, Olathe
KS 66062 phone 913-390-4500 www.scadaview.com