Keypad/display issues
Also called an SMT, the
keypad and display normally is not a maintenance problem. However, if you have
keys that don’t work or the display is garbled or won’t show data, the unit may
need to be replaced.
Troubleshooting:
It the SMT is not working correctly and showing garbled
data on the screen, try the following to reset the display:
1. Disconnect
the cable connected to the back of the unit OR power down the entire RTU.
2. Simultaneously
push and hold the . (period) 0 (zero) and up arrow keys.
3. Plug
the cable back into the unit (or power up the RTU)
4. When
the unit powers back up, it will ask if you want to load defaults. Yes, push
the up arrow (F1 key). The display should be reset and showing a normal
display.
If resetting the display does not correct the problem, it
OR the controller it is connected to may need to be replaced.