Pressure transducers
Micro-Comm pressure transducers
come in four standard pressure ranges with two configurations. The standard
ranges are 0-15 psi, 0-60 psi, 0-100 psi and 0-300 psi. The configurations are
weighted snub nose (suspended in liquid) and those with ¼ inch NPT thread,
usually connected to the source with white polyflow
tubing. Other transducers supplied by Micro-Comm
include well drawdown transducers, consult your operation manual for more
information.
Erratic
readings from transducers are often caused by clogging because of
debris in the sense line or in the holes of the weighted snub nose. Flushing
out the unit usually will clear the obstruction. For transducers connected with
polyflow tubing, disconnect the tubing from the
transducer and allow water to flow until is it unobstructed. If possible,
remove the ¼ inch fitting in the end of the transducer to flush out the inside-
be careful, the stainless steel diaphragm inside the
transducer can be easily damaged. Do not
attempt to scrape out and debris, use running water only.
When
removing and reinstalling the ¼ inch fitting on the transducer, do
not over tighten; it may crack the transducer housing. Avoid using brass
fittings in transducers if at all possible.
It is
recommended flushing of transducers at least once per year to help
insure reliable operation.
Replacement
transducers may be shipped with or without cable attached. If
cable is attached, simply pull it through the conduit, cut to length and land
wires on the terminals as they were previously connected.
If the transducer was shipped without cable, you may watch
the video here http://www.micro-comm-inc.com/Micro-Comm/support/transducer-replace.html
for easy instructions.
Testing
of transducers can be done with a voltmeter
that reads DC milliamps. With zero psi pressure input, the transducer will
output 4 milliamps. At the max rated pressure (example 100 psi) the transducer
will output 20 milliamps. Any reading between 4 and 20 is algebraically
equivalent to the psi range (example 0 to 100 psi). For example, 12 milliamps
would equal 50 psi.
To
test output of a pressure transducer:
1. Set voltmeter to read DC milliamps
2. Remove
red wire (+) at PLC.
3. Connect
black voltmeter lead to red wire
4. Connect
red meter lead to the terminal where the red wire was previously connected.
5. Read
value on the voltmeter. Remember, at zero PSI you
should read 4 milliamps. 3.95 or 4.05 or in that range is acceptable. At the
full PSI rating of the transducer (i.e., 100 psi) you will read 20 milliamps.
6. If
there is pressure on the transducer and you know that value, you can measure
the milliamps and per above, algebraically calculate to see if the transducer
is putting out the correct amount of current for the pressure applied. NOTE- if
comparing to a pressure gauge, note that many gauges are accurate only to
within 5 or 10 percent, and comparing the gauge reading to the transducer will
seem off. Remember that a working transducer is MUCH more accurate that an
analog gauge, even those that are high quality.
Copyright
2018 Micro-Comm Inc. 15895 S. Pflumm Road, Olathe KS 66062 phone 913-390-4500 www.scadaview.com